Setting 1: Feedback Loss Alarm
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a "FBL - Feedback
Low" alarm will be displayed and a digital output set for "PID feedback low" (H2-
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a "FBH - Feedback High" alarm
will be displayed and a digital output set for "PID feedback high" (H2-
an alarm output (H1-
range, the alarm and outputs are reset.
Setting 2: Feedback Loss Fault
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a "FBL - Feedback
Low" fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-
37, a "FBH - Feedback High" fault will be displayed. Both events trigger a fault output (H1-
to stop the motor.
Setting 3: Digital Output Only, Even if PID is Disabled by Digital Input
Same as b5-12 = 0. Detection is still active even if PID is disabled by a digital input (H1-
Setting 4: Feedback Loss Alarm, Even if PID is Disabled by Digital Input
Same as b5-12 = 1. Detection is still active even if PID is disabled by a digital input (H1-
Setting 5: Feedback Loss Fault, Even if PID is Disabled by Digital Input
Same as b5-12 = 2. Detection is still active even if PID is disabled by a digital input (H1-
b5-13: PID Feedback Low Detection Level
Sets the feedback level used for PID feedback low detection. The PID feedback has to fall below this level for longer
than the time b5-14 before feedback loss is detected.
No.
b5-13
b5-14: PID Feedback Low Detection Time
Sets the time that the PID feedback has to fall below b5-13 before feedback loss is detected.
No.
b5-14
b5-36: PID Feedback High Detection Level
Sets the feedback level used for PID feedback high detection. The PID feedback has to exceed this level for longer than
the time b5-37 before feedback loss is detected.
No.
b5-36
b5-37: PID Feedback High Detection Time
Sets the time for that the PID feedback has to exceed b5-36 before feedback loss is detected.
No.
b5-37
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
= 10). The drive will continue operation. When the feedback value leaves the loss detection
Name
PID Feedback Low Detection Level
Name
PID Feedback Low Detection Time
Name
PID Feedback High Detection Level
Name
PID Feedback High Detection Time
5.2 b: Application
= 3E) will be triggered. If the
= 3F) will be triggered. Both events trigger
= E) and cause the drive
= 19).
= 19).
= 19).
Setting Range
0 to 100%
Setting Range
0.0 to 25.5 s
Setting Range
0 to 100%
Setting Range
0.0 to 25.5 s
Default
0%
Default
1.0 s
Default
100%
5
Default
1.0 s
127