YASKAWA T1000V Technical Manual page 254

Ac drive for textile applications
Table of Contents

Advertisement

6.4 Fault Detection
LED Operator Display
Cause
Speed Search parameters are set to the
wrong values.
The motor is coasting in the opposite
direction of the run command.
LED Operator Display
Cause
The wrong motor code has been set
(Yaskawa motors only).
Load is too heavy.
Load inertia is too heavy.
Acceleration and deceleration times are too
short.
LED Operator Display
Cause
Parameter settings are not appropriate for
the type of load.
There is a fault on the machine side.
LED Operator Display
Cause
Parameter settings are not appropriate for
the type of load.
There is a fault on the machine side.
254
Too Many Speed Search Restarts
SEr
The number of speed search restarts exceeded the number set to b3-19.
• Reduce the detection compensation gain during Speed Search (b3-10).
• Increase the current level when attempting Speed Search (b3-17).
• Increase the detection time during Speed Search (b3-18).
• Repeat Auto-Tuning.
Enable Bi-directional Speed Search (b3-14 = "1").
Motor Pull Out or Step Out Detection
STo
Motor pull out or step out has occurred. Motor has exceeded its pull out torque.
• Enter the correct motor code for the PM being used into E5-01.
• For special-purpose motors, enter the correct data to all E5 parameters according to the Test Report
provided for the motor.
• Increase the value set to n8-55 (Load Inertia for PM).
• Increase the value set to n8-51 (Pull-In Current during Accel/Decel for PM).
• Reduce the load.
• Increase the motor or drive capacity.
Increase n8-55 (Load Inertia for PM).
• Increase the acceleration and deceleration times (C1-01 through C1-08).
• Increase the S-curve acceleration and deceleration times (C2-01).
Undertorque Detection 1
UL3
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the
allowable time (L6-03).
Check the settings of parameters L6-02 and L6-03.
Check the load for any problems.
Undertorque Detection 2
UL4
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the
allowable time (L6-06).
Check the settings of parameters L6-05 and L6-06.
Check the load for any problems.
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents