Pso Opto Output - Aerotech HPe 150 Hardware Manual

Position controllers and drives
Hide thumbs Also See for HPe 150:
Table of Contents

Advertisement

Ensemble HPe 150/200
3.2.1. PSO Opto Output
N O T E : If your Ensemble HPe 150/200 was purchased before July 2013, refer to
The PSO OPTO OUT is electrically isolated and does not require an external power source to operate. The
output may be used to source (or sink) current (as shown in
By default, JP2 is installed in the 2-3 position for normally open operation. If the PSO-NC option is ordered,
JP2 is installed in the 1-2 position giving normally-closed operation. This mode should be used with caution
since the Ensemble HPe 150/200 cannot maintain the closed state when its AC mains power is turned off.
The PSO-NC (JP2 1-2 setting) should not be used when fail-safe operation is required. JP2 jumper settings
are shown in
Table
3-10. For the JP2 jumper location, refer to
Table 3-10:
PSO Output Polarity Settings for JP2
PSO Output Polarity
Normally Open
Normally Closed
Table 3-11:
Output Specifications 
Description
Maximum Voltage
Current
Latency
Maximum Frequency
HPe/HLe
Figure 3-4:
PSO Output Sources Current
72
TB302-2
5-24V
TB302-3
LOAD
250 mA MAX
Chapter 3
-IO Expansion Board
Section 3.2.3.
Figure 3-4
and
Figure
3-5).
Figure 3-1
JP2 Setting
2-3 (Recommended)
1-2
Specification
24 V
250 mA
120 ns
5 MHz
HPe/HLe
TB302-2
TB302-3
Figure 3-5:
PSO Output Sinks Current
www.aerotech.com
5-24V
LOAD