Advanced commissioning
8.4 Adapt the default setting of the terminal strip
8.4.8
Analog output
Function description
Define the analog output type
Define the analog output type using parameter p0776.
Current output (factory setting)
Voltage output
Current output
Defining the analog output function
You define the analog output function by interconnecting parameter p0771 with a connector
output of your choice. Parameter p0771 is assigned to the specific analog output via its
index, e.g. parameter p0771[0] is assigned to analog output 0.
Connector outputs are marked with "CO" in the parameter list of the List Manual.
Example
To output the converter output current via analog output 0, you must interconnect AO 0 with
the signal for the output current.
Set p0771 = 27.
Defining the function of an analog output
Table 8-5
Parameter
r0021
r0025
r0026
r0027
r0063
You can find additional connector outputs in the parameter list.
198
Interconnecting signals in the converter (Page 461)
Frequently used connector outputs (CO) of the converter
Description
CO: Speed actual value, smoothed
CO: Output voltage, smoothed
CO: DC link voltage, smoothed
CO: Absolute actual current, smoothed
CO: Speed actual value
Overview of the manuals (Page 465)
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
p0776[0] =
0
1
2
Factory setting
- rpm
- Vrms
- V
- Arms
- rpm