Panel Controller
13.6

LED Test on modules

To test the LED display of selected modules:
1.
2.
A list of various selection criteria is offered:
Example
To test the LED displays of an LSN 300 module:
1.
2.
3.
4.
NOTICE!
The numbers before the module names indicate the slot of the module on the panel.
13.7

Network

All networked nodes that can be reached via the node currently being operated, in this
example node 1, and that are recognized within the system network are displayed under
Node.
Node
2
3
4
CAN1 to USB1 designate the interfaces on the currently operated panel node. In this example,
it is the node 1 interfaces.
The number of nodes that need to be passed in order to reach the preceding node in the list is
entered underneath the interfaces (CAN1 to USB1). In the table, node 3 under the CAN1
interface has been assigned the value 2, as the distance from node 1 to node 3 is 2 nodes
including the target node; see illustration. A value = 0 means that the node cannot be reached
via this interface.
Bosch Sicherheitssysteme GmbH
Select Diagnostics in the start menu
LED test on modules
Select LED test all modules to test the LED display of all modules.
Select By number or By type to test the LED display of individual selected modules.
Select By type.
A list of all module types is displayed.
Select the LSN 300 module.
A list of all LSN 300 modules is displayed.
Select the list field(s) you require.
The list fields are marked.
Select Activate LEDs.
The LEDs are activated for the duration of approx. five seconds.
CAN1
CAN2
1
0
2
0
0
1
Operation guide
ETH1
SER1
USB1
0
0
0
0
0
0
0
0
0
Diagnostics | en