Panel Controller
14.5

Detector removal

NOTICE!
To remove a detector, all acoustic signals and transmission devices are bypassed for 15
minutes. They are automatically un-bypassed when the 15 minutes are up.
The acoustic signals can also be manually un-bypassed before the 15 minutes are up.
To remove a detector:
1.
2.
3.
To switch the signaling devices back on before the 15 minutes are up:
1.
When the 15 minutes are up, the panel emits a brief signal tone and the start menu is
displayed.
14.6

Change device on V.24 Interface

On the V.24 interface, other devices can be optionally assigned in addition to a permanently
assigned device.
NOTICE!
After the system starts up following a power cut or battery failure, the permanently set-up
device is assigned to the V.24 interface again.
To assign a different device to the V24 interface:
1.
2.
3.
4.
14.7

Bypassing/Un-bypassing buzzer

In order to prevent an acoustic warning tone being sent to the panel during maintenance
work, for example, the panel's internal buzzer can be permanently bypassed.
To bypass the internal buzzer, select the following from the start menu:
1.
2.
To un-bypass the buzzer again, select Unbypass buzzer in step 2.
NOTICE!
If you switch the internal buzzer off permanently, no acoustic signal will sound on the panel in
the event of an alarm or fault!
Bosch Sicherheitssysteme GmbH
Select Maintenance from the start menu
Remove detector
Select OK to confirm the request. The following message appears:
All signaling and transmission devices will be inoperative for %d min
%d is used as a placeholder for the time that was defined in the FSP-5000-RPS
programming software, e.g. 15 minutes. The counter then counts from 15 minutes to zero
minutes. The detectors can be removed during this time.
Select Restore manually disabled outputs.
Select Maintenance from the start menu
Change device at V.24 interface
A list of devices is displayed.
Select the element you require in the display.
Change the device on the V.24 interface.
The device is ready for operation.
Maintenance
Bypass buzzer
The buzzer is bypassed and the text on the user interface changes to Unbypass buzzer.
Operation guide
Maintenance | en
67
F.01U.076.969 | 6.0 | 2010.04