7.2.1.3 Termination

7.2.1.4 Diagnostics

Electric Drives and Controls | Bosch Rexroth AG
The maximum length allowed for spur lines connected to the bus cable
is 6 meters. The overall length of the bus cable including all spur lines
is not to exceed the maximum length listed in the table below.
The maximum cable length depends on the baud rate and the cable
type used.
Baud rate Cable type Cable length
125 kBit/s 2 x 1.1 mm 500 m
2 x 0.6 mm 100 m
250 kBit/s 2 x 1.1 mm 250 m
2 x 0.6 mm 100 m
500 kBit/s 2 x 1.1 mm 100 m
2 x 0.6 mm 100 m

Fig. 7-19: Baud rate DeviceNet

Terminate the DeviceNet bus at both ends by terminating resistors
(120 Ohm).
A diagnostics LED is located at the rear of the small operator terminal.
The LED shows the states of the bus system.

Fig. 7-20: Arrangement of the DeviceNet diagnostics LED

The diagnostics LED at the small operator terminal has the following
functions:
Color
State
Function
Green
Off
Terminal Disconnected from Bus
Green
On
Communication Active
Green
Flashing
Sporadic Bus Error

Fig. 7-21: Function of the DeviceNet diagnostics LED