en | Bypass
11

Bypass

This chapter contains information about the following points:
WARNING!
Bypassed detectors: Alarm messages from bypassed detectors are no longer displayed, only
faults.
Isolated detectors: Isolated detectors are not analyzed.
11.1

Menu overview

Bypass
-> Bypass
Block
Block
11.2

Bypassing and un-bypassing elements

Select the element you require in the submenu.
NOTICE!
Partly bypassed elements, such as loops or bypass groups, can be displayed and completely
bypassed; see Section 11.3 Displaying and un-bypassing bypassed element groups, page 55.
NOTICE!
The menu structure may be different depending on the configuration in FSP-5000-RPS.
Example:
To bypass a detector, select the following in the start menu:
1.
2.
3.
4.
5.
F.01U.076.969 | 6.0 | 2010.04
Section 11.2 Bypassing and un-bypassing elements, page 54
Section 11.3 Displaying and un-bypassing bypassed element groups, page 55
Section 11.4 Displaying list of all bypassed elements, page 55
Section 11.5 Bypassing/Un-bypassing buzzer, page 56
-> Show bypassed devices Select by
Signalling devices
Detector
Bypass group
Bypass Block
Bypass
Detector
Various sorting criteria are displayed. See also Section 5.6 Working with lists, page 27.
Select a selection criterion, e.g. By description.
A list of the detectors is displayed. Refer to Section 5.6.1 Scrolling through lists, page 28
for information on how to scroll forward and backward through the list.
Select the required list fields.
The list fields are marked.
Operation guide
Bypass buzzer
number
Transmission
HVAC
device
Logical zone
Extinguishing
system
More...
-> Control element Interface
Panel Controller
Printer
Doorholder
Annunciator
module