Panel Controller
13.4

Hardware

13.4.1

Address cards

To display information about the released addresses:
1.
2.
3.
4.
5.
13.4.2

Display

Five different functions are offered:
LED test
To test the LEDs in the LED display:
1.
2.
3.
4.
Key test
To test the functionality of the membrane keypad:
1.
2.
3.
4.
5.
6.
Display test
To test the functionality of the display:
1.
2.
3.
4.
Bosch Sicherheitssysteme GmbH
Select Diagnostics in the start menu.
Hardware
Address cards
The information is displayed.
A status bar appears.
Select the arrow keys to display further information.
Select Refresh to update data if necessary.
LED test: Test the LED display.
Key test: Test the operativeness of the membrane keypad.
Display test: Test the operativeness of the display.
Display touch test: Test the operativeness of the touch-sensitive surface.
Adjust touch screen (calibration): Adjust the location precision when touching the touch
screen.
Select Diagnostics in the start menu
Hardware
Display
Select LED test.
For the duration of approx. five seconds, all LEDs on the LED display light up.
Select Diagnostics in the start menu
Hardware
Display
Key test
Press one or more keys on the membrane keypad.
The selected keys on the membrane keypad are depicted on the touch screen.
If a key is pressed twice, this key is shown with a black background. Press the key again
to display it without distinction.
Select Stop key test to end the foil test.
Select Diagnostics in the start menu
Hardware
Display
Select Display test.
Line by line, the display turns a dark color from the top to the bottom and then changes
again from black to white.