Test - Bosch B8512G Operation Manual

Hide thumbs Also See for B8512G:
Table of Contents

Advertisement

70
en | B94x/B93x Actions menu
16.3

Test

Use the Test menu to walk test your system, send test reports, or to
review system revision information on the keypad display.
16.3.1
Walk Test
A walk test allows you to test the sensors, keypads, sounders, and other
devices in your system without creating alarm events. You can review
untested points at the keypad to help pinpoint any problems.
You cannot turn on the security system while in the walk test mode.
Also, the security system does not create alarm events for points
included in the walk test. Points not included create alarm events. For
example, faulting a fire point during an intrusion walk test creates a fire
alarm event.
Beginning the walk test activates the burglary tone for 2 seconds. A
battery test also begins. A successful battery test ends in four minutes
(the walk test continues). If the security system determines there is a
low battery, it generates a low battery event and continues the test. If
the battery is determined to be very low, the system creates a missing
battery event and ends the battery test immediately.
To test individual detection devices, simply activate sensors and open
protected doors and windows one-at-a-time. As you fault each detection
device, the keypad from which you initiated the test emits a brief tone,
and for 60 seconds the display indicates that the point was tested. The
tone and display verify that each detection device is working properly.
Keypads within the area's scope from which you did not initiate the
walk test show Walk test in progress during the testing.
2019.06 | 07 | F.01U.307.371
Control Panels
Bosch Security Systems B.V.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B9512gB6512B5512B4512B3512

Table of Contents