Zone Message; 4: Loop Setup; Style; Loop Protocol - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Programming

Zone Message

Pressing 3 while viewing Zone Setup Screen #3 will display the following screen:
Pressing the down arrow key will display additional screens for Zones up to Z99. Press the number
key corresponding to the Zone to be programmed. Screens will be displayed allowing the
programmer to select Audio Messages 1 through 14. When an audio message is selected, the
display will return to the Zone Message screen, showing the message selected for that particular
zone. In the example above, Zone 01 has been programmed for Audio Message 1.
3.6.4 Loop Setup
PROGRAMMING
Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6, or 7 wiring and
1=LOOP SETUP
2=SYSTEM SETUP
to select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the
3=VERIFY LOOP
following screen to be displayed:
Programming Screen #2

Style

To program the SLC Style for the selected loop, press 1 for Style, while viewing Loop Setup
Screen. In the preceding example, the control panel is programmed for Style 4 SLC wiring as
indicated by the 4 to the right of Style in the display. To change the wiring style, press 1 to toggle
the display to read Style 6. Each press of the 1 key will cause the display to toggle between Style 4
and Style 6. Note that, when programming the Loop Style, the programmer can only select between
Style 4 and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop
Setup for Style 6. Style 7 wiring is the same as Style 6 with the added requirement that each
addressable device on the loop must have a pair of isolator modules, one on each side.
NOTE on SLC Troubles: If the FACP reports an open fault on an SLC Loop programmed for
Style 6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the
Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired)
to clear the SLC trouble.

Loop Protocol

Loop Protocol refers to the SLC loop mode of operation. Refer to "Wire Requirements" on
page 177 for wire specifications based upon SLC protocol. There are two Loop Protocols available:
Pressing 2 while viewing the Loop Setup Screen will toggle between CLIP and LiteSpeed
Protocols.
90
CLIP (Classic Loop Interface Protocol) - which is used for the older legacy addressable
devices such as the M300 Series modules and detectors.
LiteSpeed (factory default setting) - used for the 350 Series or newer addressable devices for
quicker response times. Note that the legacy devices can operate only in CLIP mode while the
newer devices are compatible with CLIP and LiteSpeed modes of operation.
ZONE MESSAGE
1=Z00
NO MESSAGE
2=Z01
MESSAGE 1
3=Z02
NO MESSAGE
LOOP SETUP
1=STYLE
4
2=PROTOCOL LITESPEED
Loop Setup Screen
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Master Programming Level