Master Programming Level

Zone Type

ZONE SETUP
1=ZONE TYPES
Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on

2=ZONES AVAILABLE

3=ZONE MESSAGE
the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a
Zone Setup Screen #3
screen similar to the following:
This display will show the system zones (default and user programmed) and their associated types.
Note that an up and/or down arrow will appear in the upper right corner of the display, indicating
that additional screens of zone information exists. Press the up or down arrow keys to view zones
Z00 through Z99.
Zone types can be changed by pressing the keypad number key corresponding to the zone in each
Zones Installed Screen. Available zone types will be displayed in the resultant screens. For
example, to change the zone type for zone Z02 in the screen illustrated above, press 3. The
following screens will be displayed:
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen
#2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the
Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure
for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow
silenceable zone type to the selected zone. Any signaling devices programmed to the same zone can
be silenced by pressing the Alarm Silence key or by using the auto-silence feature.
To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page 91.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will
only change how it is reported to the Central Station.
Zones Available
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
3=ZONE MESSAGE
Zone Setup Screen #3
The display will show all of the zones that are still available for programming. Note that an up
and/or down arrow may appear in the upper right corner of the display, indicating that additional
screens of zone information exists. Press the up or down arrow key to view additional screens.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
ZONE TYPE PROG
1=Z00
2=Z01
3=Z02
Zones Installed Screen
ZONE TYPE PROG
1=MONITOR
2=SMOKE PHOTO
3=WATERFLOW
Zone Type Program Screen #1
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
3=TAMPER
Zone Type Program Screen #3
ZONES AVAILABLE
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19 20 21
MONITOR
MONITOR
MONITOR
ZONE TYPE PROG
1=HEAT
2=PULL STATION
3=DUCT
Zone Type Program Screen #2
ZONE TYPE PROG
1=SUPERVISORY
2=PROC. MON
3=SMOKE ION
Zone Type Program Screen #4
Programming
89