Canadian Option; Waterflow Silenceable - Fire-Lite MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9050UD:
Table of Contents

Advertisement

Programming
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
104
While viewing the selected screen, press the number corresponding to the desired relay type to pro-
gram the main circuit board relay. The choice will be stored in memory and the display will return
to the Relay Type Screen which will show the programmed type choice. Press the Escape key to
return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Notes:
1.
AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the
Supervisory and/or Process Monitor type code, when activated, will automatically reset when
the corresponding condition is cleared.
2.
A relay programmed with the Silenceable Alarm type will activate upon any alarm and reset
when the alarm is cleared and/or when the Alarm Silence button is pressed.

Canadian Option

Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Cana-
dian requirements. The display will change to Canadian Opt. On. Each press of the 1 key will
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory default
setting is Canadian Opt. Off.
1=CANADIAN OPT.
2=WATERFLOW SIL.
For Canadian applications, remote annunciation must be done using the secondary ANN-BUS.
The Canadian Options configures the FACP with the following as required by Canada:
The following monitor module type codes are not available:
non-latching supervisory
non-latching process monitor
non-latching drill
process monitor
hazard
tornado
medical alert
The auto-silence timer can only be set to 0 or 20 minutes.
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian
specifications.
Positive Alarm Sequence, the Pre-Signal option, and their corresponding timers are not
available for Canadian applications.
The installer must write in the Date of Final Assembly on the Master Marking and Warranty
label located on the FACP backbox door.

Waterflow Silenceable

Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the sys-
tem for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the
display between Waterflow Sil. No and Yes. When Waterflow Sil. No is selected, all output devices
associated with a waterflow type input device, will be nonsilenceable. When Waterflow Sil. Yes is
selected, all output devices associated with waterflow type input devices, will be silenceable. The
factory default setting is Waterflow Sil. No.
SYSTEM SETUP
Relays Selection Screen
MS-9050 Series Manual — P/N 52413:F 10/22/2010
Master Programming Level
OFF
NO

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9050udc

Table of Contents