Auto Silence; Coding - Fire-Lite MS-9600 User Manual

Fire alarm control panel
Hide thumbs Also See for MS-9600:
Table of Contents

Advertisement

Programming
NAC #

1=AUTO SILENCE

2=CODING

TEMPORAL
NAC Screen #2
90
3.6.5.5.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit
board silenceable notification appliances after a programmed length of time. To
enable this feature and program the time delay before Auto Silence activation, press
1 while viewing NAC Screen #2. The following screens will be displayed:
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #3
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence
Screen #1. To enable the Auto Silence feature, press the number corresponding to
the time delay which will elapse before Auto Silence activates. When a time delay
is selected, the information will be stored in memory and the display will return to
NAC Screen #2.
3.6.5.5.5 Coding
The Coding feature allows the programmer to select the type of output that the main
circuit board notification appliances will generate when activated. Pressing 2 while
viewing NAC Screen #2 will cause the following displays to appear:
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
1=TEMPORAL
2=TWO STAGE
Coding Screen #2
CODING
CODING
Master Programming Level
MS-9600 PN 51335:E 7/9/03