Programming
A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss
reporting delay in hours (00 to 23 hour delay). When the second digit is entered, the display will
return to AC Loss Delay Screen #1.
NOTE:
transfer immediately, regardless of the AC Loss Delay setting. If no trouble exists at the panel
other than AC Loss, the System Trouble relay will delay its activation for the duration of the AC
Loss Delay setting.

NAC (Notification Appliance Circuit)

SYSTEM SETUP
1=TIMERS
2=NAC
The options for the NACs on the control panel main circuit board can be configure by pressing 2
3=RELAYS
while viewing System Setup Screen #2. The following screens will be displayed:
System Setup Screen #2
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3, or 4 for NAC 4.
The following screens will be displayed for each selection:
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will
prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key
will cause the display to toggle between Enabled Yes and Enabled No.
NOTE: The programming for NAC 1 will determine the operation of the remote power supply sync.
NAC #
1=ENABLED
2=TYPE
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1.
3=SILENCEABLE
The following screen will be displayed. Press the down arrow key to view additional screens:
NAC Screen #1
Select the NAC device type by pressing the number corresponding to the type in the appropriate
screen. When the selection is made, the display will return to NAC Screen #1.
96
Upon the loss of AC power at the control panel, relays programmed for 'AC Loss' will
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
NAC #
1=ZONE
00 00 00 00 00
2=SIL INHIBITED
NAC Screen #3
Enabled
Type
NACS
1=NAC 1
3=NAC 3
2=NAC 2
4=NAC 4
NAC Selection Screen
YES
1=AUTO SILENCE
BELL
2=CODING
YES
1=SYNC TYPE
2=MNS OVERRIDE
NO
NAC TYPE
1=BELL
2=HORN
3=STROBE
Type Screen #1
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Master Programming Level
NAC #
00
TEMPORAL
NAC Screen #2
NAC #
S
NO
NAC Screen #4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlseMs-9200udlsc

Table of Contents