Specifications

This section contains specifications for the system. Individual sections are provided for
CEC drawer, rack, and the I/O drawer specifications.

CEC Drawer

The mechanical packaging, cooling, power supply, and environmental requirements for
the CEC drawer are shown in the following table:
Dimensions
Height
Width
Depth
Weight
Minimum configuration
Maximum configuration
Electrical
Power source loading typical in
kVA
Power source loading maximum
in kVA
Voltage range (V ac)
Frequency (hertz)
Thermal output (typical)
Thermal output (maximum)
Power requirements (typical)
Power requirements (maximum)
Power factor
Inrush current¹
Maximum altitude²
Temperature Requirements²
Humidity Noncondensing
Without tape drive
With tape drive
Wet Bulb Requirements
Without tape drive
With tape drive
Noise Emissions³
With H80 CEC Drawer only
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete
tones
58
Service Guide
218 mm 8.58 in. (5 EIA Units)
445 mm 17.5 in.
820 mm 32.3 in.
41 kg 90 lbs.
52 kg 115 lbs.
0.32
0.48
200 to 240
50 or 60
1025 Btu/hr
1536 Btu/hr
300 watts
450 watts
0.95
40 amps
2135 m (7000 ft.)
Operating
10 to 40°C
(50 to 104°F)
Operating
8 to 80%
20 to 80%
27°C (80.6°F)
23°C (73°F)
Operating
5.8 bels
N/A
45 dBA
No
Non-Operating
10 to 52°C
(50 to 125.6°F)
Non-Operating
8 to 80%
8 to 80%
27°C (80.6°F)
27°C (80.6°F)
Idle
5.8 bels
N/A
45 dBA
No