Receive: Rxd(235) - Omron SYSMAC CJ - REFERENCE MANUAL 08-2008 Reference Manual

Programmable controllers
Hide thumbs Also See for SYSMAC CJ - REFERENCE MANUAL 08-2008:
Table of Contents

Advertisement

Serial Communications Instructions

3-24-4 RECEIVE: RXD(235)

Purpose
Ladder Symbol
PLC Setup Settings for CPU Unit's RS-232C Port
Programming
Console address
Word
Bit
162
0 to 15
No-protocol Mode Send
Delay
164
8 to 15
No-protocol Mode Start Code 00 to FF hex
0 to 7
No-protocol Mode End Code
165
12
No-protocol Mode Start Code
Specifier
8 and 9
No-protocol Mode End Code
Specifier
0 to 7
No-protocol Mode Number of
Bytes of Data
DM Setup Area Settings for Serial Communication Board's Ports
Setup Area word
Bit
Port 1
Port 2
D32002 D32012 15
0 to 14
D32004 D32014 8 to 15
0 to 7
D32005 D32015 12 to 15 No-protocol Mode Start
8 to 11
0 to 7
Reads the specified number of bytes of data from the CPU Unit's built-in RS-
232C port or one of the Serial Communications Board's serial ports. (The
Serial Communications Board must be Ver. 1.2 or later).
RXD(235)
D
C
N
Name
Name
No-protocol Mode Send
Delay Specifier
No-protocol Mode Send
Delay Time
No-protocol Mode Start
Code
No-protocol Mode End
Code
Code Specifier
No-protocol Mode End
Code Specifier
Number of Bytes of Data
D: First destination word
C: Control word
N: Number of bytes to store
0000 to 0100 hex (0 to 256 decimal)
Section 3-24
Settings
0000 to 210F hex,
0 to 99,990 ms decimal
(in 10-ms units)
00 to FF hex
0: None
1: Use start code.
0 hex: None
1 hex: Use end code.
2 hex: Use CR+LF.
00 hex: 256 bytes (default)
01 to FF hex: 1 to 255 bytes
Settings
0: Default (0 ms)
1: Use delay in bits 1 to 14.
0000 to 7530 hex
0 to 300,000 ms decimal
(in 10-ms units)
00 to FF hex
00 to FF hex
0 hex: None
1 hex: Use start code.
0 hex: None
1 hex: Use end code.
2 hex: Use CR+LF.
00 hex: 256 bytes (default)
01 to FF hex: 1 to 255
bytes
993