Low Voltage Wiring For Control Circuit Terminals - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

Drive Model
2257
FWH-600A
2313
FWH-800A
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads of approximately 150%.
Drive Model
4002
4004
4005
4007
4009
4012
4018
4023
4031
FWP-150A
4038
FWP-200A
4044
FWP-200A
4060
FWP-225A
4075
FWP-250A

Low Voltage Wiring for Control Circuit Terminals

You must provide low voltage wiring as specified by the National Electric Code (NEC), the Canadian Electric Code,
Part I (CEC), and local codes. Yaskawa recommends the NEC class 1 circuit conductor. Use the UL approved class 2
power supply for external power supply.
Input/Output
Digital input
Analog input
Analog output
Pulse train output
Pulse train input
Safe disable input
Serial communication input/output
24 V external power supply
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Fuse
Manufacturer: Bussmann
Model
Qty
2
2
Table 5.24 Recommended Fuse (Three-Phase 400 V Class)
Fuse
Manufacturer: Bussmann
Model
Qty
FWP-50B
2
FWP-50B
2
FWP-50B
2
FWP-60B
2
FWP-60B
2
FWP-60B
2
FWP-80B
2
FWP-90B
2
2
2
2
2
2
Table 5.25 Control Circuit Terminal Power Supplies
Drive Model
2360
2415
Drive Model
4089
4103
4140
4168
4208
4250
4302
4371
4414
4477
4568
4605
4720
Terminals
S1 to S8, SN, SC, SP
A1 to A3, AC, +V, -V
FM, AM, AC
MP, AC
RP, AC
H1, H2, HC
D+, D-, AC
PS, AC
5.3 UL Standards
Fuse
Manufacturer: Bussmann
Model
FWH-1000B
FWH-1000B
Fuse
Manufacturer: Bussmann
Model
FWP-300A
FWP-300A
FWP-350A
FWP-450A
FWP-600A
FWP-700A
FWP-800A
-
-
-
-
-
-
Power Supply Specifications
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Uses the LVLC power supply in the drive.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Use the UL Listed class 2 power supply.
Qty
2
2
Qty
2
2
2
2
2
2
2
5
293