B4: Timer Function - YASKAWA GA800 Maintenance & Troubleshooting

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

3.5 b: Application
No.
Name
(Hex.)
b3-33
Speed Search during Uv
Selection
(0B3F)
Expert
b3-35
Low Back EMF Detection
Level
(0BC3)
Expert
b3-36
High Back EMF Detection
Level
(0BC4)
Expert
b3-39
Regen Judgment Lv of Spd
Search
(1B8F)
Expert
b3-54
Search Time
(3123)
b3-55
Current Increment Time
(3124)
Expert
b3-56
InverseRotationSearch
WaitTime
(3126)
b3-61
Init Magnet Pole Estimation
Gain
(1B96)
Expert

b4: Timer Function

No.
Name
(Hex.)
b4-01
Timer Function ON-Delay
Time
(01A3)
b4-02
Timer Function OFF-Delay
Time
(01A4)
b4-03
Terminal M1-M2 ON-Delay
Time
(0B30)
Expert
b4-04
Terminal M1-M2 OFF-Delay
Time
(0B31)
Expert
b4-05
Terminal M3-M4 ON-Delay
Time
(0B32)
Expert
b4-06
Terminal M3-M4 OFF-Delay
Time
(0B33)
Expert
b4-07
Terminal M5-M6 ON-Delay
Time
(0B34)
Expert
b4-08
Terminal M5-M6 OFF-Delay
Time
(0B35)
Expert
160
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that starts Speed Search at start-up if the drive detects a Uv [Undervoltage] when it
receives a Run command.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Low Back EMF Detection Level. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the voltage level for Speed Search restart. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to determine the regenerative state during speed search. Usually it is not necessary to
change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive will run Speed Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive will increase the current from zero current to the setting value of
b3-06 [Speed Estimation Current Level 1].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the wait time until the drive starts inverse rotation search after it completes forward search when
you do inverse rotation search during Current Detection Speed Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness for initial motor magnetic pole calculation when A1-02 = 6 [Control Method
Selection = AOLV/PM]. Set b3-61 > 0.0 for an ordinary IPM motor.
When you use High Frequency Injection Auto-Tuning, the drive will automatically set this value.
Note:
• Set n8-35 = 1 [Initial Pole Calculation Method = High Frequency Injection] to enable this
parameter.
• When A1-02= 6 [AOLV/PM] and you do High Frequency Injection Auto-Tuning, the drive
automatically sets this parameter .
• Set n8-41 [HFI P Gain] to adjust the responsiveness for initial motor magnetic pole calculation
when A1-02 = 5, 7 [OLV/PM, CLV/PM].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ON-delay time for the timer input.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the OFF-delay time for the timer input.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time to activate the contact after the function set in H2-01 activates.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time to deactivate the contact after the function set in H2-01 deactivates.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time to activate the contact after the function set in H2-02 activates.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time to deactivate the contact after the function set in H2-02 deactivates.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time to activate the contact after the function set in H2-03 activates.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time to deactivate the contact after the function set in H2-03 deactivates.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Default
(Range)
1
(0, 1)
10%
(5 - 50%)
0.970
(0.500 - 1.000)
15%
(0 - 50%)
400 ms
(10 - 2000 ms)
10 ms
(10 - 2000 ms)
Determined by o2-04
(0.1 - 5.0 s)
5.0
(-20.0 - +20.0)
Default
(Range)
0.0 s
(0.0 - 3000.0 s)
0.0 s
(0.0 - 3000.0 s)
0 ms
(0 - 65000 ms)
0 ms
(0 - 65000 ms)
0 ms
(0 - 65000 ms)
0 ms
(0 - 65000 ms)
0 ms
(0 - 65000 ms)
0 ms
(0 - 65000 ms)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents