Construction
3.
Using the connector link cable, connect the PLC input and output connectors to each other.
Each PLC I/O connector has 2 connector terminals.
The connector link cable can be connected to either terminal.
Be sure to attach the connector cap to the unused connector terminal at the end.
(To select a connector link cable, refer to page 172.)
For each controller, up to 16 PLC I/O connectors (16 connectors × 32 points = 512 points)
NOTE
can be connected.
4.
Using the control cable, connect the controller to the PLC I/O connectors.
● One control cable can connect up to 8 PLC I/O connectors to the controller.
NOTE
● To connect 9 or more PLC I/O connectors, use 2 control cables. When connecting the
control cables to the controller use crimp-style terminals. In this case, overlap the crimp-
style terminals of both cables, and connect them to the terminals.
Control cable
Controller
Control cable
54
Connector link cable
Connector cap
13
14 15
16
9
10
11
12
SL-VCU1
5
6
7
8
1
2
3
4
PLC I/O connectors
(8 Nos., max.)
PLC I/O connectors
(8 Nos., max.)
Total: 16 Nos., max.