Construction

Connection of local power supply unit

Considering various conditions (total current consumption, voltage drop, etc.), if you judge that a local power
supply unit is necessary for the S-LINK V system, connect a local power supply unit.
DANGER
Observe the following items to connect a power supply unit:
● Select a power supply unit having short-circuit protective function (fuse, etc.).
● The power of the S-LINK V system passes through the inside of each unit and is then supplied to
the main cable or I/O device side.
However, the short-circuit protective function is not adopted for this power supply circuit.
● Do not connect the main power supply to the local power supply, or connect two local power sup-
plies.
● Before starting the wiring work, be sure to turn off the power. If the power is not turned off, the sys-
tem may be shorted or damaged, and you may get an electric shock.
● Take care that wrong wiring will damage the product.
● If power is supplied from a commercial switching regulator, ensure that the frame ground (F.G.)
terminal of the power supply is connected to an actual ground.
● Do not use during the initial transient time after the power supply is switched on.
● For the control units (PLC, personal computer, etc.) to which the S-LINK V units are connected,
separate power supply units that conform to the specifications of the control units are needed. For
a detailed description, refer to the instruction manual of each unit.
● If it takes a long time to turn on or off the power, use a timer relay so that the power can be sup-
plied after stabilization.

Local power supply to system

Supply local power to the S-LINK V system from the I/O terminal or a commercial junction terminal block.
Be sure to supply stabilized power (24V DC ±10%).
<To supply local power to I/O terminal>
Local power supply
<To supply local power to main line>
58
A C
F . G
.
Insulated
Local power supply
A C
F . G
.