Flowchart for power supply condition check

Check the power supply conditions.
Check the terminal
screws for looseness. Check the
power supply line for disconnec-
tion and short-circuit.
No problem detected
Check the connection condi-
tion of the power supply line.
No problem detected
Check that the power is supplied.
Supplied
Check that the
supply voltage of the con-
troller is in the range of 22.8
to 26.4V DC.
In the range
Check that the
supply voltage of the I/O
unit is in the range of 21.6
to 26.4V DC.
In the range
Replace the controller.
Problem
detected
Tighten the terminal screws, or
replace the power supply line.
Problem
detected
Correctly connect the power
supply line.
Not supplied
Supply the power.
Out of the range
Reexamine the construction of the
power supply system.
Refer to page 23 and following pages.
Out of
the range
Troubleshooting
165