Specifications
No.
Designation
Hexadecimal number
1
display mode indicator
(Green)
Transmission mode
2
indicator (Green)
3
Power indicator (Green)
4
Error indicator (Red)
5
Address display (Red)
6
SELECT keys
7
ENTER key
8
Mode selector switch
S-LINK V terminal block
9
connector
80
Indicates the current display mode of the address display.
• ON: The hexadecimal number display mode is selected.
• OFF: The decimal number display mode is selected.
This indicator will blink during transmission (when the transmission signal is being output).
The indicator blinking cycle depends on the transmission mode.
Lights up when the power is supplied from the PLC to the SL-VFP2.
This indicator indicates the error status as follows:
• Lights up when an error occurs.
• Blinks when the cause of the error is eliminated.
• Lights off when operation is normal.
The displayed item depends on the mode ('RUN,' 'CHECK,' or 'CONFIG' mode).
Use the mode selector switch to switch the mode.
<RUN mode>
• Each transmission mode (3 modes in total) will be indicated by the following character, and the LED of
each character will sequentially light up just like rotating clockwise.
A Mode
• If an error occurs, the error message will appear.
Note: After eliminating the cause of the error, press ENTER key and SELECT keys (2 types of keys) at
the same time. The error message will disappear.
<CHECK mode>
• The number of connected nodes will be displayed first. After that, each time you press SELECT key,
the recognized addresses will be displayed one after another.
Number of connected nodes:
Using the decimal or hexadecimal number, the number of I/O units' nodes will be displayed.
Address:
Using the decimal or hexadecimal number, the addresses of the I/O units will be displayed sequentially.
Note: In the hexadecimal number display mode, the hexadecimal number indicator (green) will light up.
• If an error occurs, the number of nodes having the error and the error addresses will be displayed se-
quentially (for errors 3, 4, and 5).
<CONFIG mode>
• Settings will be displayed sequentially. To switch the displayed setting, use SELECT key.
• When the RUN mode is switched to CONFIG mode, different item will be displayed compared with the
displayed item just after power-on.
Use these keys to switch the displayed item or set item.
Also use these keys to change the set condition value.
Press ENTER key to determine the set condition value.
In the system setting mode, press and hold ENTER key for 3 seconds or more. The system will be set.
Switches the mode (RUN, CHECK, or CONFIG mode).
7: G
6: D
5: 0V
Receives +24V, 0V, and F.G. from the external power supply unit, and supplies +24V, 0V,
4: +24V
D, and G to the I/O units.
3: 0V
2: +24V
1: F.G.
Function