Panasonic S-LINK V User Manual page 100

Flexible wire-saving system
Hide thumbs Also See for S-LINK V:
Table of Contents

Advertisement

Specifications
● Specifications
Type
Model No.
Supply voltage
Unit side
Current
consumption
Input side
When all points are ON,
(Note 1)
including current input
Allowable passing cur-
rent (Note 2)
Address setting
Input
Number of input points
Power supply
Green LED (lights up when there is power between the "24V DC" power supply terminal and "0V", and between "+" and "-")
Transmission
Input
Ambient temperature
Ambient humidity
Noise immunity
Voltage withstandability
Insulation resistance
Vibration resistance
Shock resistance
Mounting
Tightening torque
Material
Weight
Notes: 1) The current consumption value shown in the 'Unit side' area indicates the current consumption in the main circuit.
2) Each value includes the current consumption of this terminal and connected machine.
3) If this product is stored in the control panel together with the other units, the temperature may rise above the specified operation tem-
perature due to the heat generated by the other units.
In this case, install a cooling fan, etc. so that the ambient temperature can be in the specified range.
100
4-channel
SL-VTB4
24V DC±10% (Supplied from S-LINK V controller or separate power supply)
25mA or less
30mA or less
45mA or less
75mA or less
When all points are ON,
including current input
Total: 1A or less
Total: 2A or less
Photo-coupler input:
• Current input: 9mA or less
• Operation voltage:
ON voltage: 17V or more (between +24V and input)
OFF voltage: 4V or less (between +24V and input)
• Input impedance: Approx. 3.3kΩ
4 points
Green LED (blinks when the synchronization signal is sent from the S-LINK V controller)
Green LED (lights up when the input signal of the corresponding channel is turned ON)
-10 to +55°C (No dew condensation or icing allowed) (Note 3), Storage: -20 to +70°C
Power line: 500Vp, 10ms cycle, 1μs pulse width
Common: 1,000Vp, 10ms cycle, 1μs pulse width (with noise simulator)
1,000V AC for one min. between all terminals connected together and enclosure
20MΩ, or more, with 500V DC megger between all terminals connected together and enclosure
10 to 150Hz frequency, 0.75mm amplitude or maximum acceleration 49m/s² in X, Y and Z directions for two
hours each
2
490m/s
acceleration (approx. 50G) in X, Y and Z directions for three times each
Installed on DIN rail or by tightening screws
Terminal screw: 0.5N・m or less, Mounting screw: 1.2N・m or less
Approx. 90g
Approx.130g
8-channel
16-channel
SL-VTB8
SL-VTB16
35mA or less
150mA or less
When all points are ON,
including current input
Total: 4A or less
Using switches, in the range of 0 to 511
8 points
16 points
35 to 85% RH, Storage: 35 to 85% RH
Enclosure: ABS, Terminal area: PBT
Approx. 220g
32-channel
SL-VTB32
45mA or less
300mA or less
When all points are ON,
including current input
Total: 7A or less
32 points
Approx. 225g