Panasonic S-LINK V User Manual page 29

Flexible wire-saving system
Hide thumbs Also See for S-LINK V:
Table of Contents

Advertisement

<In case of SL-VFP2, SL-VMEL-Q, SL-VPCI, SL-VVMES2>
Input
I/O device
• Sensor
• Switch
1.
Response time of input device (sensor, etc.)
• Relay, etc.
2.
 
S-LINK V system
PLC etc.
● Response delay of S-LINK V system
• Input response time (2 + 3 + 4 + 5)
MIN.
MAX.
• Output response time (7 + 8 + 9)
<Table 1 Filtration time>
Filtration time (ms)
A mode
B mode
MIN.
MAX.
MIN.
0.05
0.06
0.19
Input
0.2ms
3.
Filtration
4.
Refresh time
5.
Internal memory
Max. 1 refresh time
2
3
= 0.2 + From Table 1 + From Table 2 + From Table 2 (ms)
= 0.2 + From Table 1 + From Table 2 + From Table 2 (ms)
7
MIN.
= From Table 2 + From Table 2 +
MAX.
= From Table 2 + From Table 2 +
C mode
MAX.
MIN.
MAX.
0.26
0.77
1.02
6.
PLC / PC operation time (scanning time)
4
8
0.35 (ms)
0.35 (ms)
<Table 2 Refresh time, Internal memory max.1 refresh time>
Refresh time, Internal memory max.1 refresh time (ms)
Number of
I/O control
A mode
points
MIN.
MAX.
32
1.50
64
2.09
96
2.68
128
3.27
160
3.85
192
4.44
224
5.03
256
5.62
0.29
288
6.21
320
6.79
352
7.38
384
7.97
416
8.56
448
9.15
480
9.73
512
10.32
Transmission Delay Time
Output
10. Response time of
output device
(actuator, etc.)
9.
Output
0.35ms
8.
Refresh time
7.
Internal memory
Max. 1 refresh time
5
9
B mode
C mode
MIN.
MAX.
MIN.
6.01
8.36
10.71
13.06
15.42
17.77
20.12
22.47
1.18
4.70
24.82
27.18
29.53
31.88
34.23
36.58
38.94
41.29
MAX.
24.03
33.44
42.85
52.26
61.66
71.07
80.48
89.89
99.30
108.70
118.11
127.52
136.93
146.34
155.74
165.15
29