Specifications
● Specifications
Type
Model No.
Snap male connector
Applicable connector
SL-CP1, SL-CP2, SL-CP3
Supply voltage
Current consumption
Allowable passing current
(Note)
Address setting
Output
Output operation
Short-circuit protection
Number of output points
Power
Transmission
Output
Output holding function
Ambient temperature
(Note 3, 4)
Ambient humidity
Noise immunity
Voltage withstandability
Insulation resistance
Vibration resistance
Shock resistance
Mounting
Tightening torque
Material
Cable
Weight
Accessory
Notes: 1) Each value includes the current consumption of this unit and connected machine.
2) If one of the output channels is shorted, the short-circuit protective function will be activated to protect all the channels, and outputting
signals to the external machine will be stopped. Eliminate the cause of the problem, and the system will be automatically restored.
3) If this product is stored in the control panel together with the other units, the temperature may rise above the specified operation tem-
perature due to the heat generated by the other units.
In this case, install a cooling fan, etc. so that the ambient temperature can be in the specified range.
4) In some cases, you cannot install the same connector output units close to each other, or connector output units and other I/O units
close to each other. The distance between these units depends on the ambient temperature.
While referring to the following figure, secure enough distance between the units.
<To horizontally install the units>
8
6
Units
4
2
0
-10 0
10 20 30 40 5055
Ambient temperature (°C)
112
4-channel
Connector type
e-CON connector type
SL-VTP4J
e-CON conforming con-
nector
24V DC±10% (Supplied from S-LINK V controller or separate power supply)
60mA or less (when all points are ON)
NPN open-collector transistor (photo-isolation)
• Maximum sink current: 200mA
• Applied voltage: 30V DC or less (between output and 0V)
• Residual voltage: 1.5V or less (at 200mA sink current)
The output transistor will be turned on if the output signal is sent from the signal transmission line.
4 points
Green LED (lights up when the power is supplied)
Green LED (blinks when the synchronization signal is sent from the S-LINK V controller)
Orange LED (lights up when the output signal of the corresponding channel is turned ON)
-10 to +55ºC (No dew condensation or icing allowed), Storage: -20 to +70ºC
Power line: 500Vp, 10ms cycle, 1µs pulse width
Common: 1,000Vp, 10ms cycle, 1µs pulse width (with noise simulator)
1,000V AC for one min. between all terminals connected together and enclosure
20MΩ, or more, with 500V DC megger between all terminals connected together and enclosure
10 to 150Hz frequency, 0.75mm amplitude or maximum acceleration 49m/s² in X, Y and Z directions for two
hours each
2
490m/s
acceleration (Approx. 50G) in X, Y and Z directions for three times each
Mounted on DIN rail or by tightening screws
Approx. 75g
L=25
L
L=20
L
L
L=15
L=10
L=0
L=5
Connector type
SL-VTP4E
SL-VTP8J
Snap male connector
SL-CP1, SL-CP2, SL-CP3
90mA or less (when all points are ON)
Total: 2A or less
Using switches, in the range of 0 to 511
0.4V or less (at 16mA sink current)
Incorporated (Note 2)
Incorporated
35 to 85% RH, Storage: 35 to 85% RH
Mounting screw: 0.8N·m or less
Enclosure: ABS, Installation base: POM
2
0.5mm
4-core flat cable, 0.6m long
Connector I/O unit mounting base: 1 pc.
<To vertically install the units>
8
6
4
2
0
-10 0
Ambient temperature (°C)
8-channel
e-CON connector type
SL-VTP8E
e-CON conforming con-
nector
8 points
Approx. 80g
L=20
Units
L=15
L
L
L=10
L
L=5
L=0
10 20 30 40 5055