Fagor DDS Series Hardware Manual page 356

Table of Contents

Advertisement

   Connection diagrams
Diagram of the maneuver
Important.
- KA3 is a relay for a delayed deactivation
of contactor - KM1 (t seconds) in order to
be able to keep it closed long enough to
return to mains (with XPS power supply)
t he excess ene rgy gener ated while
braking the motor.
10.
Make sure that the delay "t" programmed
at relay - KA3 is slightly longer than the
braking time of the application.
The delay disconnection time "t" to be
programmed at relay - KA3 must be
greater than the total amount of time
required to brake the motor to a full stop.
Note. CNC EMERG. will always be assigned to I1/O1 of the PLC with an 8055/55i CNC. With an 8070 CNC, it may
be assigned to any I/O of the PLC. The contacts associated with relays - KA2 and - KA3 are shown in fig.
and fig.
F. H10/30
AXD/SCD mixed system, SERCOS/CAN. Diagram of the maneuver.
358
DDS
HARDWARE
Ref.1912
· 356 ·
See parameter GP9
in the "man_dds _soft.pdf" manual.
.
F. H10/29
+24VDC
X+
KA1
X-
Z+
Z-
KM1
ON
OFF
EMERG.
STOP
XPS
SYSTEM OK
S_SCD
DR.S OK
-KM1
-KA2
SYSTEM
SPEED
I1 PLC
SPEED
ENABLES
ENABLE
CNC EMERG.
O1 PLC
-KA1
EMERGENCY LINE
GND
KA1
KA3
KA2
KA2
KA2
ON
OFF
Green
Red
DELAY
OFF
-KA3
t seconds
DRIVE
(See GP9)
ENABLES
BRK
(See GP9)
ON
OFF
BRAKE LINE
F. H10/28