Climatic considerations
The temperature inside the electrical cabinet containing the DDS system must
not exceed 55°C/131°F (60°C/140°F with power reduction).
MANDATORY. Never install the DDS system next to a heat source.
The modules generate heat and when trying to decide whether the electrical
cabinet containing the DDS system needs external cooling or not, one must
know the power dissipated by each one of its modules. See next table
T. H8/1 Power dissipated by the modules of the DDS system.
Power supplies
PS-65A
PS-25B4
XPS-25
XPS-65
RPS-80
RPS-75
RPS-45
RPS-20
Auxiliary modules
APS-24
CM-1.75
ER+TH-x/x y
ER+TH-18/x+FAN
MAIN FILTER 42A-A
MAIN FILTER 75A-A
MAIN FILTER 130A-A
MAIN FILTER 180A-A
Modular drives
AXD/MMC 1.08
AXD/MMC 1.15
AXD/MMC 1.25
AXD/MMC 1.35
AXD/MMC 2.50
AXD/MMC 2.75
AXD/MMC 3.100
AXD/MMC 3.150
MMC 3.200
SPD 1.15
SPD 1.25
SPD 1.35
SPD 2.50
SPD 2.75
SPD 2.85
SPD 3.100
SPD 3.150
SPD 3.200
SPD 3.250
Compact drives
ACD/CMC 1.08
ACD/CMC 1.15
ACD/CMC 1.25
ACD/CMC 2.35
ACD/CMC 2.50
SCD 1.15
SCD 1.25
SCD 2.35
SCD 2.50
SCD 2.75
Power dissipated at
maximum load
Dissipated power
It depends on the activation frequency
of the Ballast protection circuit.
Power dissipated at 4/8 kHz
156/195 W
225/305 W
270/389 W
351/510 W
536/605 W
834/840 W
110/130 W
195/201 W
349/350 W
289/333 W
432/438 W
496/546 W
626/668 W
1163/1187 W
1333/1344 W
Power dissipated at 4/8 kHz
110/139 W
160/206 W
220/295 W
123/123 W
150/150 W
215/220 W
275/315 W
289/333 W
   Installation
8.
.
275 W
180 W
180 W
350 W
1 000 W
1 000 W
700 W
500 W
60 W
0 W
19 W
20 W
40 W
61 W
33/44 W
69/89 W
88/132 W
98/98 W
DDS
40/50 W
HARDWARE
87/118 W
Ref.1912
· 263 ·