AS Ser ies M od ul e Man ua l
11.5.6.4.
Software Diagnosis
Click the Start Monitor button on the AS01DNET (RTU) interface. The Error code column will show relevant contents as
follows.
11
Error No.
0x8001
0x8002
Note: For details on more error codes, refer to the explanation of Error ID in AS-series product manual.
Remark:
The software diagnosis function can not be enabled until the DeviceNet Builder software is online.
11 - 9 6
Explanation
AS01DNET (RTU) can not
detect the configured module.
Current
module
is
not
consistent with the configured
module.
Solution
1. Check if the module is disconnected.
2. Check if the module is damaged.
Ensure that the actually connected module is the same as
that configured in the software.