When the analog output signal changes, the system updates the value of the analog output according to
the value set in the slope, as shown in the image below.
Analog si gnal
*The output conversion time and the input channel sampling cycle are the same.
5.
Scale Range
You can set the scale range when the format is floating-point. The analog output mode of a channel has
a corresponding digital range. Digital values correspond to analog outputs sent by the module. For
example, if the analog range is -10 V to +10 V, the digital range is -10.0 to +10.0, the HSP scale is 10.0,
and the LSP scale is -10.0. The digital values -10.0 to +10.0 correspond to the analog values -10 V to
+10 V, as the example below shows.
Analog value
10 V
Rated output range
-10 V
-10.0
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
Time
10.0
Scale range
Digital value
5_
5 - 1 9