After the master assigns mapping addresses to AS01DNET (RTU), the mapping devices of the modules connected
to the right side of AS01DNET (RTU) are shown as below.
The software automatically assigns mapping addresses of module parameters in the arrangement order of modules
connected to the right side of AS01DNET (RTU) from left to right.
Below is the table of configuration of one master AS01DNET and one slave AS01DNET (RTU) and mapping addresses
that the software automatically assigns to each module. D26005 and D26105 are the control word and status word of
AS01DNET (RTU).The input mapping address and output mapping address of AS16AP are D26006 and D26106
respectively. The input mapping addresses and output mapping addresses of AS04DA are D26007~D26008 and
D26107~D26114 respectively. The input mapping addresses of AS04AD are D26009~D26018.
Auto Assignment
AS01DNET(RTU)
AS16AP
AS04DA
AS04AD
The input and output mapping addresses of AS01DNET (RTU) are D26005~D26018 and D26105~D26114.
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Input
D26005 status word
D26006
D26007~D26008
D26009~D26018
Output
D26105 control word
D26106
D26107~D26114