AS Ser ies M od ul e Man ua l
9.7.2.3 ERROR LED Indicators Blinking Every 0.5 Seconds
Error codes:
Error
Code
16#1500
Remote module communication timeout
16#1502
Incorrect parameters
Remote extension module communication
16#1503
timeout
The actual placement of the extension
16#1505
modules is NOT the same as it is set.
9.7.2.4 ERROR LED Indicators Blinking Every 0.2 Seconds
This happens when the 24 VDC power supply for the remote module is not sufficient. Check the power supply. If the
power supply is normal, remove the extension module from the CPU module and then check if the SCM remote
module is out of order. Error codes:
Error
Code
24VDC power supply had not been
16#1303
sufficient before and then recovered from
low-voltage that was less than 10 ms.
_9
9 - 7 8
Description
Description
Solution
Make sure the communication cable is well connected
Check the parameter in HWCONFIG. Download the
parameter again.
Make sure the communication cable is well connected
and the module is properly connected to the CPU
module and turn the modules on again.
Check if the parameter in HWCONFIG is the same as
the actual placement.
Solution
Check whether the 24 V power supply to the module is
normal.