Type
IO-Link
Event
Warning Error
Codes
16#8CA8
V
V
16#8CA9
V
16#8CAA
V
16#8CAB
16#8CAC
V
0xFF21
0xFF22
0xFF23
0xFF24
0xFF25
Ch ap te r 13 IO- Li nk Co mm un ica tio n M odu le AS04 SIL
Event
Notifica-
tion
Device power supply
voltage under-run L+
(<9V)
Illegal device ID
HWCONFIG configured
process data exceeding
the IO-Link process
data range
IO-Link process data
exceeding HWCONFIG
configured process
data range
Data storage error
V
New connected device
V
Device disconnected
Data storage
V
identification mismatch
Data storage not
V
sufficient
Data storage parameter
V
access denied
Solution
Check the external power
supply
Check device
specifications
Check device
specifications
Scan the device and
download the configuration
again
Contact the factory
Check installation
Set the Data Storage
access locked and set it to
backup / restore and then
backing up data according
to actual placement.
Check device
specifications
Check device
specifications