Delta AS Series Manual page 85

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

3.5 Troubleshooting
3.5.1 Error Codes
Error
Code
16#1605
Hardware failure
16#1607
The external voltage is abnormal.
16#1608
The factory calibration is abnormal.
16#1801
The external voltage is abnormal.
16#1802
Hardware failure
16#1804
The factory calibration is abnormal.
The signal received by channel 1 exceeds the range of inputs
16#1808
that the hardware can receive.
The signal received by channel 2 exceeds the range of inputs that
16#1809
the hardware can receive.
The signal received by channel 3 exceeds the range of inputs that
16#180A
the hardware can receive.
The signal received by channel 4 exceeds the range of inputs that
16#180B
the hardware can receive.
The signal received by channel 5 exceeds the range of inputs that
16#180C
the hardware can receive.
The signal received by channel 6 exceeds the range of inputs that
16#180D
the hardware can receive.
The signal received by channel 7 exceeds the range of inputs that
16#180E
the hardware can receive.
The signal received by channel 8 exceeds the range of inputs that
16#180F
the hardware can receive.
-
When power-on, the module is not detected by CPU module.
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
Description
A  D LED
ERROR LED
Indicator
Indicator
OFF
ON
OFF
ON
OFF
ON
OFF
Blinking
Blinking
OFF
Blinking
OFF
Run: blinking
Blinking
Stop: OFF
Blinking once
or twice and
after 2
OFF
seconds, it
blinks
repeatedly
3 - 4 1