Arrangement Of Terminals; As04Ad Control Register - Delta AS Series Manual

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

A S S er i es Mo d u le Ma n ua l

3.2.3 Arrangement of Terminals

V 1+
I1 +
_3
V I1
-
V 3+
I3 +
-
V I3
S LD
A G

3.2.4 AS04AD Control Register

*If you use HWCONFIG to set values in CRs, once the set value is downloaded, the values can be retained in
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
power failure or after transition of the CPU from STOP to RUN.
Note: The attribute of the CR must be W (write) to use TO instruction.
CR#
0
Format Setup
1
Channel 1 mode setup
Channel 2 mode setup
2
Channel 3 mode setup
3
Channel 4 mode setup
4
3 - 6
AS04AD-A
04AD
V 2+
P WR
I2 +
E RR
V I2
-
A
D
V 4+
I4 +
V I4
-
S LD
2 4V
0 V
Name
0: integer format
1: floating point format
0: closed
1: -10 V to +10 V
2: 0 V–10 V
3: -5 V to +5 V
4: 0 V–5 V
5: 1 V–5 V
6: 0 mA–20 mA
7: 4 mA–20 mA
AS08AD-B
08AD
V1+
V2+
PWR
-
-
V1
V2
ERR
V3+
V4+
A
D
-
-
V3
V4
V5+
V6+
-
-
V5
V6
V7+
V8+
-
-
V7
V8
AG
24V
0V
Description
AS08AD-C
08AD
I1+
I2+
PWR
-
-
I1
I2
ERR
I3+
I4+
A
D
-
-
I3
I4
I5+
I6+
-
-
I5
I6
I7+
I8+
-
-
I7
I8
AG
24V
0V
Atr.
Defaults
R
0
R/W
1