Status Word Diagnosis - Delta AS Series Manual

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

80 means AS01DNET (RTU) is in STOP state.
02 is the node ID: 2 of AS01DNET (RTU).
11.5.6.3.

Status Word Diagnosis

The status word of AS01DNET (RTU) shows the operation states of special modules and digital I/O modules. See the
following table for status word diagnosis and disposal.
Status
Bit
value
0
AS01DNET (RTU) is in RUN state
bit0
1
AS01DNET (RTU) is in STOP state.
Valid
0
AS01DNET(RTU)
bit1
Invalid configuration data in AS01DNET
1
(RTU)
bit2
Reserved
——
bit3
Reserved
——
Currently connected module matches the
0
configuration in the software.
bit4
Currently
1
inconsistent with the configuration in the
software.
0
AS01DNET(RTU) in normal operation
bit5
1
AS01DNET(RTU) in low voltage
bit6
Reserved
——
0
AS01DNET(RTU) in normal operation
bit7
Reserved
——
bit8
Reserved
——
bit9
Reserved
——
bit10
Reserved
——
bit11
Reserved
——
bit12
Reserved
——
bit13
Reserved
——
bit14
Reserved
——
bit15
Reserved
——
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Description
configuration
data
connected
module
Disposal
No correction needed
Restart AS01DNET(RTU)
in
No correction needed
Re-download
the
configuration
AS01DNET (RTU) by using the DeviceNet
Builder software.
——
——
No correction needed
1. Check if currently connected module is
consistent with the configuration in the
software.
is
2. Change current module to match the
configuration in the software or change the
configuration in the software to match
currently connected module.
No correction needed
Check if the power supply for AS01DNET (RTU)
is normal.
——
No correction needed
——
——
——
——
——
——
——
——
——
11
data
to
11 - 9 5