AS Ser ies M od ul e Man ua l
9.6.4 Remote IO Application (AS-FEN02)
When the firmware is V2.02 or later, AS-FEN02 can be installed on AS00SCM-A (RTU mode) and then PLC can
monitor right side IO modules remotely.
Device
AS300
AS00SCM-A + AS-FEN02
AS08AM10N
AS08AN01T
AS04AD-A
AS04DA-A
Step 1
After setting up AS300 in ISPSoft and HWCONFIG. Open EIP Builder and scan the network to add AS00SCM-A
(RTU) + AS-FEN02 to the Network. Double-click RTU module to open HWCONFIG and scan to obtain the
configuration and mapped register addresses of the I/O module on the right side of AS00SCM-A. You can also edit
the module configurations and write down the mapped register addresses. After saving, close HWCONFIG. Refer to
Section 9.4.2.3 for more details.
_9
9 - 7 2
Function
IP Address / Location
EtherNet/IP Master
EtherNet/IP Slave
Digital Input
right side of AS00SCM-A
Digital Output
right side of AS00SCM-A
Analog Input
right side of AS00SCM-A
Analog Output
right side of AS00SCM-A
Data Mapping Range
192.168.1.5
D29000~D29019
192.168.1.3
D29060~D29079
D29080~D29099
X1.0~X1.15
Y1.0~Y1.15