Delta AS Series Manual page 459

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Parameters Setting and Device Explanation
Setup for AS01DNET-A
Parameter
Setting value
Node ID
Baud rate
500 kbps
Setup for VFD-C2000
Parameter
Setting value
00-20
00-21
09-30
09-70
09-71
PLC Program
S1: The number of the module sending DeviceNet communication. The first one of the right side is 01.
S2:DeviceNet node ID (MAC ID); Node ID of VFD-C2000: 01.
S3:Service code; 0X0E: read one single attribute content.
S4:Class ID; Class ID of CMC-DN01: 01;
S5:Instance ID; Instance ID of CMC-DN01: 01;
S6:Attribute ID; Attribute ID of CMC-DN01: 01;
S7:Write data size. When DNETRW instruction is used to read data, the value in S7 can be set to any
data.
S8:The start device where the written data are stored. When DNETRW instruction is used to read data,
the value in S8 can be set to any data.
S9:Communication timeout time
S10: Times of re-transmission. Times of re-sending communication when communication timeout occurs.
D1:Completion flag
00
Set the node ID of AS01DNET-A to 00.
Set the baud rate of AS01DNET-A to 500 kbps.
08
Frequency command source
05
Operation command source
0
Communication decoding method
01
Node ID of AC motor drive
02
Baud rate: 500Kbps
Description
Description
11
11 - 3 3