AS Ser ies M od ul e Man ua l
Step 6
Double click the module icon and the Node Configuration window appears. Click Error Control Protocol and then
Error Control Setting windows appears. Select Heartbeat and set values for the Master Consumer Timeout and
Node Heartbeat Producer Timer. Select AH10COPM Master from the Node List and click the Down arrow to add it
to the list of Heart Consumer and then disconnection detection is now available for AS00SCM-A (RTU mode).
Click OK to confirm the setting. Download the parameters to the PLC. And then PLC can control the input/output of
the IO module remotely.
_9