Ems Standards - Delta AS Series Manual

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

AS Ser ies M od ul e Man ua l
1.2.2

EMS Standards

_1
1.2.2.1 EMI
Port
Enclosure port
(radiated)
(measured at a
distance of 10
meters)
AC power port
(conducted)
1.2.2.2 EMS
Environmental
Phenomenon
Electrostatic
Discharge
Radio Frequency
Electromagnetic Field
Amplitude
Modulated
Power Frequency
Magnetic Field
1 - 6
Frequency Range
Level (Normative)
30-230 MHz
40 dB (μV/m) quasi-peak
230-1000 MHz
47 dB (μV/m) quasi-peak
79 dB (μV) quasi-peak
0.15-0.5 MHz
66 dB (μV) average
73 dB (μV) quasi-peak
0.5-30 MHz
60 dB (μV) average
Reference Standard
IEC 61000-4-2
80% AM,
IEC 61000-4-3
sinusoidal
IEC 61000-4-8
Reference Standard
IEC 61000-6-4
Test
Contact
Air
2.0-2.7 GHz
1.4-2.0 GHz
1 kHz
80-1000 MHz
60 Hz
50 Hz
Test Level
±4 kV
±8 kV
1 V/m
3 V/m
10 V/m
30 A/m
30 A/m

Hide quick links:

Advertisement

Table of Contents
loading