To connect the AC power cords to the device for each power supply (see
1. Locate or obtain the power cords you will use with the services gateway. The power cords must have
a plug appropriate for your geographical location.
2. Wrap and fasten one end of the ESD grounding strap around your bare wrist, and connect the other
end of the strap to the ESD point on the chassis.
3. Move the AC switch next to the appliance inlet on the power supply to the off position (O).
4. Insert the appliance coupler end of the power cord into the appliance inlet on the power supply.
5. Insert the power cord plug into an external AC power source receptacle.
NOTE:
Each power supply must be connected to a dedicated AC power feed and a
dedicated external circuit breaker. We recommend that you use a 15 A (250 VAC) minimum,
or as permitted by local code.
6. Dress the power cord appropriately. Verify that the power cord does not block the air exhaust and
access to device components, or drape where people could trip on it.
7. Repeat Step
1
through Step
Figure 88: Connecting AC Power to the Services Gateway
6
for the remaining power supplies.