6.4.2

Invert setpoint

Procedure
Interconnect parameter p1113 with a binary signal,
e.g. digital input 1.
Table 6- 23
Parameter
p1113 = 722.1
p1113 = 2090.11
6.4.3

Inhibit direction of rotation

In the factory setting of the inverter, both motor directions of rotation are enabled.
Set the corresponding parameter to a value = 1 to permanently block directions of rotation.
Table 6- 24
Parameter
p1110 = 1
p1110 = 722.3
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Examples of settings to invert the setpoint
Remark
Setpoint inversion
Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Converter inverts the setpoint.
Invert setpoint via control word 1, bit 11.
Examples of settings to inhibit the direction of rotation
Remark
Inhibit negative direction
Negative direction is permanently inhibited.
Inhibit negative direction
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.

Advanced commissioning

6.4 Setpoint calculation