Technical data

11.3 General converter technical data

11.3
General converter technical data
Property
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Line impedance uk
Inrush current
Overvoltage category
Line harmonics
Pulse frequency (factory setting) FSA ... FSG
1086
Explanation
FSA ... FSG:
● for systems according to IEC:
3 AC 380 V (-20 %) ... 480 V (+10 %)
3 AC 500 V (-20 %) ... 690 V (+10 %)
● for systems according to UL:
3 AC 380 V ... 480 V
3 AC 500 V ... 600 V
The actual permissible line voltage depends on the installation altitude.
FSH, FSJ:
● 3 AC 380 V (-15 %) ... 480 V (+10 %)
● 3 AC 500 V (-15 %) ... 690 V (+10 %)
0 V 3 AC ... line voltage x 0.97
47 Hz ... 63 Hz
● FSA ... FSG: 0 Hz ... 550 Hz, depending on the control mode
● FSH/FSJ: 0 Hz ... 150 Hz, depending on the control mode
● FSA ... FSG: 0.75 ... 0.93
● FSH/FSJ with line reactor uk = 2 %: 0.75 ... 0.93
4 %
< 2 × peak input current
The converter can withstand 100,000 power cycles with an inverval of 120 s.
According to IEC 61800-5-1:
● III for Power Module
● III for Control Unit (Not for corner grounded network 380-480V AC or power supply
network >= 600V AC without electrical isolation)
The converter fulfils the requirements of IEC 61000-3-12 with Rsce = 120.
Further technical data on request.
● 400 V converters:
4 kHz for devices with an LO base load power < 100 kW
2 kHz for devices with an LO base load power ≥ 100 kW
● 690 V converters: 2 kHz
FSH/FSJ: 4 kHz