Receive Data - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

No.
6
7
8
3841 Encoder does not support the function
14.4.6.20

Receive data

Overview
The converter writes the receive data of the set telegram to signal sources designated for that
purpose.
Requirement
You have activated communication via fieldbus and set a telegram.
Description of function
The converter stores the receive data as follows:
• "Word" format in r2050
• "Double word" format in r2060
The converter automatically interconnects parameters r2050 and r2060 with the signals
corresponding to the telegram.
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Explanation
Passive homing interrupted
Fetch measured value canceled
Actual position value transfer canceled
14.4 PROFINET communication
Possible cause
Reference cam has not been configured
A switch was made to active homing during pas‐
sive homing.
During passive homing, the request "Read value x"
was received.
More than one value was requested.
No value requested.
Requested value is not available.
Encoder is parked.
No absolute encoder available.
Alarm bit set in the absolute value protocol.
---
Functions
363