8.7.3.4

Test stop

Testing failsafe I/O
Failsafe I/O must be tested at defined intervals in order to validate their failsafe state (test
stop or forced dormant error detection). For this purpose, SINAMICS S110 contains a
function block which carries out this forced dormant error detection when selected via a
BICO source. A timer is started after every error-free test stop to monitor the time until the
next required test. After this time interval (p10003) has expired, and each time the Control
Unit is switched on, the user is notified via message A01774 that a test stop must be
performed for the F-DI/DO.
● Three test stop modes can be selected for testing the output (see following sections).
● The failsafe digital inputs must be checked by whoever carries out the forced dormant
Carrying out a test stop:
Proceed as follows to parameterize the test stop:
1. Determine the appropriate test stop mode for the circuits used in your application (see
2. Set the test stop mode which is to be used via parameter p10047.
3. Use parameter p10046 to define whether the digital output F-DO 0 is to be tested.
4. Set the debounce time for the digital inputs using parameter p10017.
5. Use parameter p10001 to set the time within which the digital output signals to the
6. Use parameter p10003 to set the interval within which a test stop should be carried out.
7. Set the signal source which triggers the start of the test stop using parameter p10007.
While the test stop is being carried out, the message A01772 (test stop failsafe inputs /
outputs active) appears. The messages A01772 and A01774 only disappear again after the
test stop has been performed. If an error is found during the test stop, fault F01773 is output.
Using the test sequence specified for each test stop mode, you can see which error has
occurred from the fault value of the test step.
Duration of test stop
You can calculate the duration of the test stop by using this formula:
T
Test stop
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
error detection.
diagrams in the following sections).
corresponding digital inputs or DIAG inputs must be recognized.
After this time interval has expired, you will be notified via message A01774 that a test
stop must be performed for the F-DI/DO.
This can be, for example, a control signal or switch via a BICO switchable signal.
= 3 · p10000 + 2 · (3 ms + p10017) + 8 · p10000 + 6 · (p10001 + p10017)
Test of the
Evaluation of the
F-DIs
inactive F-DIs
Safety Integrated Functions
Test of the
Evaluation of the
F-DO
active F-DIs
8.7 Commissioning
441