No.
4.
Analyze trace:
SOS is triggered after the SS2 timer (p9352/9552) has expired.
5.
Save/print the trace and add it to the acceptance report (refer to the example below)
6.
Deselect SS2
Ensure that the drive is running with the setpoint again
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7])
Example Trace SS2
Figure 8-40
Example Trace SS2
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Description
Safety Integrated Functions
8.9 Acceptance test and acceptance report
Status
487