Safety Integrated Functions
8.9 Acceptance test and acceptance report
8.9.2.3

Test scope for specific measures

Table 8- 21
Scope of partial acceptance tests for specific measures
Measure
A) Documentation
Replacement of
Yes, Points 1 and 2
the encoder
system
Replacement of
Yes, Points 1 and 2
an SMC/SME
Replacement of
Yes, Points 1 and 2
a motor with
DRIVE-CLiQ
Replacement of
Yes, Points 1 and 2
the Control Unit
/ power unit
hardware
Replacement of
Yes, Points 1 and 2
the Power
Module or Safe
Brake Relay
Firmware -
Yes, only Point 2
upgrade(CU /
power unit/
Sensor
Modules)
Change to a
Yes, Points 4 and 5. Yes, test the
single
parameter of a
safety function
(e.g. SLS limit)
Transfer of
Yes
project data to
other machines
(series
commissioning)
Note
Forced dormant error detection functional testing (C) and actual value acquisition functional
testing (D) together represent the "simplified function test" mentioned in previous chapters.
466
B) Functional testing
C) Functional testing
of safety functions
of forced dormant error
detection
No
No
No
No
No
No
No
Yes, only Point 1
Yes, Points 1 or 2
Yes, only Point 1
and 3
Yes, if new safety
Yes
functions are to be
used
No
appropriate function
Yes, but only testing
Yes
of the selection of
the safety functions
D) Functional
testing of actual
value acquisition
Yes
Yes
Yes
Yes, only Point 1
Yes, only Point 1
Yes, only Point 1
Yes
Yes
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
E) Conclusion
of the report
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes