Trace evaluation:
● SLS function with SLS level 1 is active (see bits "deselection SLS", "selection SLS bit 0",
● Drive is accelerated beyond the SLS limit (time axis from approx. -800 ms)
● Exceeding of the limit is recognized (time axis 0 ms)
● Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
● Fault response STOP B is initiated (time axis 0 ms; see bit "STOP A or B active" and
● Drive is decelerated to a standstill (see orange curve of r9714[0])
● Standstill reached (time axis from approx. 600 ms)
● STOP A (as follow-up response to STOP B) is activated (see bit "STO active"); at this
● SBR monitoring is activated after 250 ms
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level
bit 1")
"SS1 active")
point the speed falls below the shutdown speed SS1 (p9560/p9360)
Note
Small time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.