9.5 Communication using USS
ADR
The ADR range is a single byte which contains the address of the slave node (e.g. inverter).
The individual bits in the address byte are addressed as follows:
Special
telegram
● Bit 5 is the broadcast bit.
Note
The Broadcast function is not supported in the current software version.
● Bit 6 = 1 indicates a mirror telegram.
Bit 5 = 0, bit 6 = 0 and bit 7 = 0 indicate normal data communication for devices. The node
address (bit 0 to bit 4) is evaluated.
BCC
BCC stands for Block Check Character. It is an exclusive OR checksum (XOR) over all
telegram bytes with the exception of the BCC itself.
9.5.5

User data range of the USS telegram

Basic parameters for communication with USS protocol via the RS485 interface
p2020
p2021
p2022
p2023
p2029
p2030
p2035
p2040
r2050
p2051
r2053
p2080 ... p2089 BI: Binector-connector converter, status word x
r2090 ... r2099
644
7
6
5
Mirror
Broadcast
bit
telegram
The node address is evaluated and the addressed slave returns the telegram to the
master unchanged.
Fieldbus interface baud rate: 2400 ... 187500 baud
Fieldbus interface address: 0 ... 30
Fieldbus interface USS PZD number: 0 ... 2 ... 16 words
Fieldbus interface USS PIV number:
[0 no PKW component, 3 (3 words), 4 (4 words), 127 (variable length)]
Fieldbus interface error statistics: 0 ... 7 ()
Fieldbus interface protocol selection: (0 no protocol, 1 USS, 2 PROFIBUS)
Fieldbus interface USS PIV Drive object number
Fieldbus interface monitoring time: 0 ... 65535 ms. 0 = no monitoring
CO: IF1 PROFIdrive PZD receive word
CI: IF1 PROFIdrive PZD send word
IF1 PROFIdrive diagnostics PZD send word
BO: IF1 PROFIdrive PZD1 receive bit-serial
4
3
2
5 Address bits
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
1
0
Function Manual