Acceptance test for Safe Operating Stop (SOS)
Table 8- 35
"Safe Operating Stop" function
No.
Note:
The acceptance test must be individually conducted for each configured control.
The control can be realized via terminals or via PROFIsafe.
1.
Initial state
Drive in "Ready" state (p0010 = 0)
Safety Integrated Extended Functions enabled (p9601.2 = 1)
Safety functions enabled (p9501.0 = 1)
SOS inactive (r9722.3 = 0)
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]); see note "non-
critical alarms" in section Acceptance test.
2.
It may be necessary to take measures in the higher-level control to be able to run the drive with activated
SOS.
Please ensure that the internal limits r9733.0 and r9733.1 are canceled by the selection "Start acceptance
test".
3.
Configure and activate trace recording.
Trigger: Trigger on variable - bit pattern (r9722.7 = 0)
Record the following values: r9713[0], r9720, r9721, r9722
Select the time interval and pretrigger so you can recognize start-up of the drive and
infringement of the SOS tolerance window (p9330/p9530)
For better analysis, display the following bit values:
r9720.3 (deselect SOS)
r9721.12 (STOP A or B active)
r9722.0 (STO active; set for STOP A)
r9722.1 (SS1 active; set for STOP B)
r9722.3 (SOS active)
r9722.7 (internal event; set on the occurrence of the first Safety message)
Select SOS
Run the drive beyond the standstill limit set in p9330/p9530
Check that the drive moves briefly and then decelerates back to a standstill
Check whether the following Safety messages are pending:
C01707, C30707 (Tolerance for safe operating stop exceeded)
C01701, C30701 (STOP B initiated)
C01700, C30700 (STOP A initiated)
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Description
Safety Integrated Functions
8.9 Acceptance test and acceptance report